logo

Recloser Residual Current Circuit Breaker (Intelligent Reclosing Type)-TDK3EL

MCCB stands for Molded Case Circuit Breaker which provides protection against overload, short circuit faults and is also used for switching the circuits. The wide current ratings and high breaking capacity in MCCB find their use in industrial applications.

 

MCCB can be used for protection of capacitor bank, generator protection and main electric feeder distribution. It offers adequate protection whenever an application requires discrimination, adjustable overload setting or earth fault protection.

Highlights

ModelTDK3EL-125CYTDK3EL-250CYTDK3EL-400CYTDK3EL-630CYTDK3EL-800CY
TDK3EL-125CSTDK3EL-250CSTDK3EL-400CSTDK3EL-630CSTDK3EL-800CS
Frame grade current Inm(A)125250400630800
No. of poles3P+N3P+N, 2P3P+N3P+N3P+N
Rated operating voltage Ue: (V)AC 400/50Hz
Rated insulation voltage Ui (V)1000
Rated impact withstand voltage (V)8000
Flashing distance (mm)≯50≯100
Limit short circuit breaking capacity Icu (kA)50    70(H)65    85(H)65
Operating short circuit breaking capacity Ics (kA)35     50(H)42    65(H)42
Rated residual short circuit on (off) capacity I△m (kA)12.5    17.5 (H)16.25    21.5(H)16.25
Rated short-time withstand current Icw (kA)/S1.5358
Residual current operating characteristicsAC type
Rated residual operating current I△n (mA)50/100/200/300/400/500/600/800 100/200/300/400/500/600/800/1000 
MCU automatic tracking or manual settingMCU automatic tracking or manual setting
Residual operating time characteristicsDelayed/non-delayed type
Limit non-drive time of delayed type (s)0.06/0.1/0.2 Optional: 2I△n
Breaking time (s)I△n≤0.5; 2I△n≤0.2; 5I△n≤0.15
Auto re-closing time (s)20-60
Operational performance (times)Powered150010001000
Not powered850070004000
Total1000080005000
Overload and short circuit characteristicsThree-stage protection, electronically adjustable, see "Description of Protection characteristics" for details
Overvoltage protection value (V)Setting value (250~300)±5%
Undervoltage protection value (V)Setting value (145~200)±5%
Link control delay time (ms)≤40ms
Communication delay time (ms)≤200ms

Talk To Us

    *We respect your confidentiality and all information are protected.

    *Please upload only jpg, png, pdf, dxf, dwg files. *Size limit is 10MB.