Model | TDK3ELG-125 | TDK3ELG-250 | TDK3ELG-400、TDK3ELG-630 | TDK3ELG-630 | TDK3ELG-800 | |
Frame grade current Inm(A) | 125 | 250 | 400、630 | 630 | 800 | |
No. of poles | 3P+N | |||||
Rated operating voltage Ue: (V) | AC400 50Hz | |||||
Rated insulation voltage Ui (V) | 1000 | |||||
Rated impulse withstand voltage (V) | 8000 | |||||
Flashing distance (mm) | ≯50 | ≯100 | ||||
Ultimate short circuit breaking capacity Icu (kA) | 25 35 (H) | 50 70 (H) | 65 85 (H) | 65 85 (H) | 65 85 (H) | |
Operating short circuit breaking capacity Ics (kA) | 17.5 22 (H) | 35 50 (H) | 42 55 (H) | 50 65 (H) | 42 55 (H) | |
Rated residual short circuit on (off) capacity I△m (kA) | 6.25 8.75 (H) | 12.5 17.5 (H) | 16.25 21.25 (H) | |||
Rated short-time withstand current Icw (kA)/S | 3 | 400:5 | 8 | 10 | ||
630:5 | ||||||
Residual current operating characteristics | AC type | |||||
Rated residual operating current I△n (mA) | 30~1000/Auto | |||||
Residual operating time characteristics | Delayed/non-delayed type | |||||
Limit non-drive time of delayed type (s) | 0.10.5 | |||||
Operational performance (times) | Powered | 1000 | 1000 | 500 | ||
Not powered | 7000 | 4000 | 2500 | |||
Total | 8000 | 5000 | 3000 | |||
Overload and short circuit characteristics | Three-stage protection, electronically adjustable, see "Description of Protection characteristics" for details | |||||
Overvoltage protection value (V) | Set value (231 ~ 330V)/default value 282V | |||||
Undervoltage protection value (V) | Set value (88 ~ 209V)/default value 187V | |||||
Phase loss protection value (V) | Set value (10 ~ 130V)/default value 30V |